Deskripsi
LUTRON DW-6195 3-Phase Power Analyzer
Features
- Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W.
- 3 current probes (CP-1201) are included, if change the current probes, the calibration procedures are not necessary.
- Current probe input signal/ranges with selection:
– Input signal (ACV): 200mV/300mV/500mV/1V/2V/3V.
– Ranges (ACA): 20A/200A/2000A/30A/300A/3000A 60A/600A/6000A - Meter can cooperate the universal current probes.
- Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe ( CP 1201 ), AC to DC 9V adapter, 2G SD memory card and Carrying bag.
- Measurement:
– V (phase-to-phase), V (phase-to-ground)
– A (phase-to-ground)
– KW / KVA / KVAR / PF (phase)
– KW / KVA / KVAR / PF (system)
– KWH / KVAH / KVARH / PFH (system)
– Phase angle - Harmonics display (1-50th order).
- Simultaneous display of Harmonics and Waveform.
- Display of Waveform with Peak Values.
- Analysis of Total Harmonic Distortion (THD).
- Graphic Phase diagram with 3-Phase system parameters.
- 3 phase Voltage or Current Unbalanced Ratio (VUR, AUR) and Unbalanced Factor.
- Calculated Unbalanced Current through Neutral Line (An).
- Capture Transient events (including Dip, Swell and Outage) with programmable threshold (%).
- Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
- ACV input impedance is 10 Mega ohms.
- Safety Standard: IEC 1010, CAT III 600V.
- Built-in clock and Calendar, real time data record with SD memory card, sampling time set from 2 to 7200 seconds. Just slot in the SD card into the computer, it can down load the all the measured value with the time information (year, month, data, hour, minute, second) to the Excel directly, then user can make the further data analysis by themselves.
- Powered by AA (UM-3) DC 1.5 V x 8 batteries (Alkaline type) or DC 9V adapter.
- Computer data output, can cooperate with optional USB Cable/USB-01, RS232 cable/UPCB-02 and Data Acquisition software, SW-811, SW-U811.
- Optional current probes: CP-1201, CP-2000, CP-200, CP-3000.
- User can order the meter only (without the current probes) with the special request as intend to cooperate their own current probes.
- Patent
Specifications
Circuit | Custom one-chip of microprocessor LSI circuit. | |
Display | *LCD Size: 81.4 x 54 mm (3.2 x 2.1 inch) *TFT LCD (320 x 240 pixels) with back light. |
|
Measurement | *V (phase-to-phase) *V (phase-to-ground) *A (phase-to-ground) *KW/KVA/KVAR/PF (phase) KW/KVA/KVAR/PF (system) KWH/KVAH/KVARH/PFH (system) *Power factor *Phase angle *Frequency *Harmonics display |
|
Wire Connections | 1P/2W, 1P/3W, 3P/3W, 3P/4W. | |
Voltage Ranges | 10 ACV to 600 ACV, auto range. | |
Current Probe Input Signal and Range | *Current probe input signal voltage (ACV): 200mV/300mV/500mV/1V/2V/3V. *Current probe input current range (ACA): 20A/200A/2000A (1200 A)/30A/300A/3000A 60A/600A/6000A *Meter can cooperate the universal current probe. |
|
Safety Standard | IEC1010 CAT III 600 V. | |
ACV Input Impedance | 10 Mega ohms | |
Range Select | ACV | Auto range. |
ACA | Manual range. | |
Clamp Frequency Response | 40 Hz to 1 KHz. | |
Spec. Tested Frequency | 45 to 65 Hz. | |
Over Load Protection | ACV | 720 ACV rms |
ACA | 1300 ACA with clamp probe *for the Clamp ,CP-1201 |
|
Data Hold | Freeze the display reading. | |
Data Record | SD Card Record. | |
Sampling Time | Approx. 1 second. | |
Power ON/OFF | Manual OFF by push button. | |
Over Indicator | *LCD display show “OL”. *The data save into the SD card will show “9999” or “999” (overleap the decimal point). |
|
Under Indicator | *The data save into the SD card will show “9999” or “999” (overleap the decimal point). | |
Real Time Data Logger | *Real time data logger, saved the data into SD memory card and download the all the measured value with the time information (year/month/data/hour/minute/second) download to the Excel. | |
*Sampling time for data logger: 2 seconds to 7200 seconds, the during of setting step are 2 seconds. | ||
Data Output USB/RS232 *Computer Interface |
RS232 computer serial interface: *Connect the optional USB cable USB-01 will get the USB plug. *Connect the optional RS232 cable UPCB-02 will get the RS232 plug. |
|
Operating Temperature | 0°C to 50°C (32°F to 122°F). | |
Operating Humidity | Less than 80% R.H.. | |
Power Supply | *DC 1.5V, AA (UM-3) Battery x 8 PCs (Alkaline or heavy-duty battery). *AC to DC 9V power adapter. |
|
Power Consumption | *Meter: 362 DC mA. *Clamp: 22 DC mA. |
|
Clamp Max. Conductor Size | 50 mm (2.0 inch) Dia. *for the Clamp ,CP-1201 |
|
Weight | *Meter: 840g (meter only) *Clamp (included cable): 500g |
|
Dimension | Meter: 225 x 125 x 64 mm (8.86 x 4.92 x 2.52 inch) | |
Clamp: 210 x 64 x 33 mm (8.3 x 2.5 x 1.3 inch) | ||
Clamp Jaw: 86 mm (3.4 inch)- outside | ||
Accessories Included | *Instruction manual…………… 1 PC *Test Leads (TL88-4AT)……….. 1 Set (4 PCs) *Alligator clips (TL88-4AC) 1 Set (4 PCs) *Clamp Probe (CP-1201)……… 3 PCs *AC to DC 9V adapter…………….. 1 PC *SD card (4G)……………….. 1 PC *Carrying bag…………………….1 PC |
|
Optional Accessories | *2000 Amp current probe, CP-2000 *200 Amp current probe, CP-200 *Flexible 3000 Amp current probe, CP-3000, CP-3002 *USB Cable , USB-01 *RS232 cable, UPCB-02 *Data Acquisition software, SW-U811 |
|
Datasheet |
Ulasan
Belum ada ulasan.