Deskripsi
HIOKI PQ3100-94 Power Quality Analyzer
Hioki portable power meters and analyzers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The PQ3100 is a comprehensive but easy-to-use power quality analyzer for monitoring and recording power supply anomalies, allowing their causes to be quickly investigated, and also for assessing power supply problems such as voltage drops, flicker, harmonics, and other electrical issues.
Key Features
- Record data including voltage, current, power, harmonics, and flicker simultaneously along a single time axis
- Measure up to 6000A AC
- Capture all power anomalies, including instantaneous outages, voltage drops, and frequency fluctuations, while simultaneously recording trend data
- Quick Set: Easy-to-understand on-screen guide for measurement procedures
- Bundled PQ ONE application software makes it easy to create reports
- Record waveforms for up to 1 second before and 10 seconds after an anomaly occurs
- Accurately measure DC currents over extended periods of time (with an AC/DC auto-zero current sensor)
- Directly supply power to connected current sensors
- Send measured values to Hioki data loggers using a Bluetooth® wireless technology compatible adapter (LR8410 Link-compatible products), Ver. 2.0 and later
Features
Remote Monitoring of a Site’s Power Supply Quality [GENNECT One SF4000]
Get measurement results from the job site in real-time, and display/save them on your PC. Immediately and automatically transfer power supply quality event measurement files to your PC. The power quality analyzer itself can be remotely controlled from your PC to change event conditions.
Value Kits Model: POWER QUALITY ANALYZER KIT PQ3100-94
Model No. (Order Code) PQ3100-94
Kit contents: AC Flexible current sensor CT7045 (6000 A) ×4, PQ3100 main unit, SD Memory card 2GB Z4001, Carrying case C1009
Note: Select from Value Kits for added savings.
Specifications
Measurement Line Type | Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement) |
Voltage Ranges | Voltage measurement: 1000.0V rms or DC, Transient measurement 2.200kV peak |
Current Ranges | 50.000mA AC to 5.0000kA AC, 10.000A DC to 2.0000kA DC (depends on current sensor in use) |
Power Ranges | 50.000W to 6.0000MW (determined automatically based on current range in use) |
Basic Accuracy | Voltage: ±0.2% of nominal voltage, Current: ±0.1% rdg. ±0.1% f.s. + current sensor accuracy, Active power: DC ±0.5% rdg. ±0.5% f.s. + current sensor accuracy, AC ±0.2% rdg. ±0.1% f.s. + current sensor accuracy |
Measurement Items | 1. Transient over voltage: 200kHz sampling 2. Frequency cycle: Calculated as one cycle 3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle 4. Voltage swell, Voltage dips, Voltage interruption, RVC (Ver.2.0 or later): Voltage (1/2) RMS calculation 5. Inrush current: half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle. 6. Frequency 200ms: Calculated as 10 or 12 cycles 7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10s period 8. Voltage waveform peak, Current waveform peak 9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor 10. Voltage crest factor, Current crest factor 11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50th orders 12. Harmonic voltage-current phase angle: 1th to 50th orders 13. Total harmonic distortion factor (voltage/ current) 14. Inter harmonic (voltage/ current): 0.5th to 49.5th orders 15. K Factor (multiplication factor) 16. IEC Flicker, Δ V10 Flicker |
Record | Maximum recording interval: 1-year, Maximum number of recordable events: 9999 × 365 days |
Interfaces | SD/SDHC memory card, RS-232C (for communication/ LR8410 link), LAN (HTTP server/ FTP/ Send e-mail), USB 2.0 (for communication) |
Logger Connectivity | Sends measured values wirelessly to logger by using a Bluetooth® wireless technology serial conversion adapter. (Supported devices: Hioki LR8410 Link-compatible loggers), Ver. 2.0 and later |
Display | 6.5-inch TFT color LCD (640 × 480 dots) |
Power Supply | AC adapter Z1002 (100V to 240V AC, 50/60Hz, rated current 1.7A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter) |
Dimensions and Mass | 300 mm (W) × 211 mm (H) × 68 mm (D), 2.5 kg (including battery pack) |
Included Accessories | Instruction manual ×1, Measurement guide ×1, Voltage cord L1000-05 ×1 set (Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5), Color clip (for identifying clamp sensor color) ×1 set, Spiral tube ×5, AC adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, PQ ONE (software, CD) ×1 |
Ulasan
Belum ada ulasan.