Deskripsi
Kyoritsu KEW 4506 Intelligent Socket Tester
Perfect socket tester that finds out the difficult-to-detect N-E Reverse connection!
- Easy measurement by simply plugging into a socket outlet and pressing the test button
- In only 1 second you can check voltage, correct wiring and polarity of Line, Neutral and Earth of a socket outlet
- KEW 4506 can be used on TT earth system, and also on TN-S by combined use with KEW 8343 (See measurement principle)
- Unique measurement method with low test current for avoiding tripping of RCDs
Specification
Socket Test *1 |
||||
---|---|---|---|---|
Measurable range of power supply voltage |
80 to 290V rms (50/60Hz) *The tester gives voltage warning if 253V or higher voltage is detected but it can perform socket test. |
|||
Socket type | 3 Pole | 2 Pole | ||
Judgement | PASS | PASS | PASS | |
FAIL | L-N Reverse | L-N Reverse< | ||
L-E Reverse | Abnormal voltage | |||
N-E Reverse | – | |||
E Not connected | – | |||
N Not connected | – | |||
N-E unjudgeable | – | |||
Abnormal voltage | – | |||
AC V (L-N) |
||||
Range | 80 to 290V rms (50/60Hz) | |||
Accuracy | ±2%rdg±4dgt | |||
Loop Resistance (N-E) |
||||
Range (Auto-ranging) | 200Ω: 0.0 to 199.9Ω 2000Ω: 200 to 1999Ω |
|||
Test current | 200Ω: 5mA (5.3 Hz) 2000Ω: 1mA (5.3 Hz) |
|||
Accuracy | ±3%rdg±5dgt | |||
Applicable standards | IEC 61010-1, IEC 61010-2-030 CAT Ⅱ 300V Pollution degree 2, IEC 60529(IP40) | |||
Operating temperature and humidity range |
-10 to 50°C, relative humidity 85% or less (no condensation) | |||
Storage temperature and humidity range |
-20 to 60°C, relative humidity 85% or less (no condensation) | |||
Power sourcebr | LR6 (AA)(1.5V) × 2 | |||
Dimension | 212(L) × 56(W) × 39(D) mm | |||
Weight | Approx. 250g (including batteries) | |||
Accessories | KAMP10 or 7284 (Test lead with IEC connector) *3 9161 (Carrying case) LR6 (AA) × 2, Instruction manual |
|||
Optional accessories | 8343 (Signal Source for Intelligent Socket Tester) |
*1 If N-E resistance measurement function is turned off (*2), test is performed with a test voltage applied from an optional
signal source only: current flows between N-E is less than 1µA
*2 If the function is disabled, KEW 4506 doesn’t show resistance between N-E.
*3 KAMP 10(AU): Australian plug / KAMP 10(EU): European SCHUKO plug / KAMP 10(UK): British plug(13A) / 7284: American(NEMA)plug
Ulasan
Belum ada ulasan.